60 cbm LPG horizon storage tank Painting Process
The surface of the LPG (Liquefied Petroleum Gas) storage tank body shall be coated with two coats of epoxy iron oxide primer and one coat of acrylic grey intermediate primer, followed by two coats of acrylic metallic topcoat. The warning sign “NO SMOKING OR OPEN FLAMES” shall be stenciled on the middle section of the tank, and “Next Inspection Date: YYYY/MM” shall be stenciled on the lower part of the saddle support.
60 cbm LPG horizon storage tank Packaging and Transportation
Packaging and transportation shall strictly comply with the regulations of JB/T 4711-2003 “Coating, Shipping and Packaging for Pressure Vessels”.
60 cbm LPG horizon storage tank Optional Safety Accessories
Safety valves, magnetic flap liquid level gauges, pressure gauges, thermometers, shut-off valves, etc.
60 cbm LPG horizon storage tank Manufacturing Process
Quality Authentication: Rigorous quality authentication is conducted on the pressure element materials, external dimensions, weld quality, operational performance, installation quality, internal devices, and safety accessories of the product.
Non-Destructive Testing (NDT): Non-destructive testing is performed on all welded joints, weld seams, tank heads, and various pressure-retaining components. Only products that pass these inspections are permitted to leave the factory, thereby guaranteeing product quality.
Heat Treatment & Testing: Before the application of the topcoat, the product undergoes stress-relief annealing heat treatment at 620°C, followed by hydrostatic testing and airtightness testing to ensure the safe application of the product.
60 cbm LPG horizon storage tank Installation
Due to their classification as special equipment, the installation of LPG storage tanks is subject to specific regulatory requirements. Installation personnel must hold nationally recognized fire safety qualifications to engage in the relevant installation work.
During the equipment installation process, strict adherence to mandatory regulations—such as fire separation distances—is required, with a primary focus on engineering quality. All associated systems, including piping, electrical, firefighting, water supply and drainage, and lightning protection facilities, must pass inspection by the supervisory authorities before being placed into service.
60 cbm LPG horizon storage tank Specifications:
| Item | Data |
| Filling Medium | Liquefied Petroleum Gas (Propane) / LPG (Propane) |
| Volume / Capacity | 60 m³ |
| Design Pressure | 1.77 MPa |
| Design Thickness of Shell | 14 mm |
| Design Thickness of Dish Ends | 16 mm |
| Main Material / Base Metal | Q345R |
| Corrosion Allowance | 1 mm |
| Heat Treatment Method | Stress-relief heat treatment (Post-Weld Heat Treatment / PWHT) |
| Tare Weight of Tank | 12,750 kg |
| Maximum Filling Weight | 25,200 kg |
| Overall Dimensions (ID × WT × L) | 2728×14×10962mm |
| Filling Factor / Filling Ratio | 0.95 |
| Hydrostatic Test Pressure | 2.22 MPa |
| Service Life / Design Life | 20 years |
| Medium Density | 420 kg/m³ (at 50°C) |
| Governing Standards / Codes | GB 150 Pressure Vessels; Supervision Regulation on Safety Technology for Pressure Vessels |
| Optional Safety Accessories | Safety valves, magnetic flap liquid level gauges, pressure gauges, thermometers, shut-off valves, etc. |
Available Capacities: 10 m³, 15 m³, 20 m³, 25 m³, 40 m³, 50 m³, 60 m³, 80 m³, 100 m³, 120 m³, 200 m³, etc. Custom designs are also available based on specific user requirements.